Don’t underestimate carbon tracing when diagnosing a short circuit fault.
Initially I found a bad electric heater that was causing a 400 amp 3 pole breaker to trip. I removed the fuses for the heater and it would still intermittently trip the breaker with increasing frequency. Even with the fuses removed there is a path between the terminals due to carbon from a previous arc flash. Once I disconnected the wiring from the terminals the breaker didn’t trip and the unit ran normally.
Initially I found a bad electric heater that was causing a 400 amp 3 pole breaker to trip. I removed the fuses for the heater and it would still intermittently trip the breaker with increasing frequency. Even with the fuses removed there is a path between the terminals due to carbon from a previous arc flash. Once I disconnected the wiring from the terminals the breaker didn’t trip and the unit ran normally.